Section 12
General function block features
12.1
Definite time characteristics
12.1.1
Definite time operation
The DT mode is enabled when the
Operating curve type
setting is selected either as "ANSI
Def. Time" or "IEC Def. Time". In the DT mode, the
TRIP
output of the function is
activated when the time calculation exceeds the set
Trip delay time
.
The user can determine the reset in the DT mode with the
Reset delay time
setting, which
provides the delayed reset property when needed.
The
Type of reset curve
setting has no effect on the reset method when the
DT mode is selected, but the reset is determined solely with the
Reset
delay time
setting.
A060764-ANSI V1 EN
Figure 293:
Operation of the counter in drop-off
1MRS240050-IB C
Section 12
General function block features
REF615R
567
Technical Manual