module (rising edge of the
PICKUP
input detected), and simultaneously
CB_FAULT_AL
is active. The operation of the backup logic depends on the
CB failure mode
setting.
•
If the
CB failure mode
is set to "Current", the activation of
TRBU
depends on the
CB
failure trip mode
setting.
•
If
CB failure trip mode
is set to "1 out of 3", the failure detection is based on any
of the phase currents exceeding the
Current value
setting. Once
TRBU
is
activated, it remains active for the time set with the
Trip pulse time
setting or
until the values of all the phase currents drop below the
Current value
setting,
whichever takes longer.
•
If
CB failure trip mode
is set to "1 out of 4", the failure detection is based on
either a phase current or a residual current exceeding the
Current value
or
Current value Res
setting respectively. Once
TRBU
is activated, it remains
active for the time set with the
Trip pulse time
setting or until the values of all
the phase currents or residual currents drop below the
Current value
and
Current value Res
setting respectively, whichever takes longer.
•
If
CB failure trip mode
is set to "2 out of 4", the failure detection requires that
a phase current and a residual current both exceed the
Current value
and
Current value Res
setting respectively or two phase currents exceeding the
Current value
. Once
TRBU
is activated, it remains active for the time set with
the
Trip pulse time
setting or until the values of all the phase currents drop
below the
Current value
, whichever takes longer.
In most applications, "1 out of 3" is sufficient.
•
If the
CB failure mode
is set to "Breaker status", the
TRBU
output is activated if the
circuit breaker is in the closed position. Once activated, the
TRBU
output remains
active for the time set with the
Trip pulse time
setting or the time the circuit breaker
is in the closed position, whichever is longer.
•
If the
CB failure mode
setting is set to "Both",
TRBU
is activated when the "Breaker
status" or "Current" mode conditions are satisfied.
The activation of the
BLOCK
input deactivates the
TRBU
output.
Section 5
1MRS240050-IB C
Protection-related functions
324
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...