3.9.2
Binary input inversion
The parameter
Input # invert
is used to invert a binary input.
Table 36:
Binary input states
Control voltage
Input # invert
State of binary input
No
0
FALSE (0)
Yes
0
TRUE (1)
No
1
TRUE (1)
Yes
1
FALSE (0)
When a binary input is inverted, the state of the input is TRUE (1) when no control voltage
is applied to its terminals. Accordingly, the input state is FALSE (0) when a control
voltage is applied to the terminals of the binary input.
3.9.3
Oscillation suppression
Oscillation suppression is used to reduce the load from the system when a binary input
starts oscillating. A binary input is regarded as oscillating if the number of valid state
changes (= number of events after filtering) during one second is equal to or greater than
the set oscillation level value. During oscillation, the binary input is blocked (the status is
invalid) and an event is generated. The state of the input will not change when it is blocked,
that is, its state depends on the condition before blocking.
The binary input is regarded as non-oscillating if the number of valid state changes during
one second is less than the set oscillation level value minus the set oscillation hysteresis
value. Note that the oscillation hysteresis must be set lower than the oscillation level to
enable the input to be restored from oscillation. When the input returns to a non-oscillating
state, the binary input is deblocked (the status is valid) and an event is generated.
Table 37:
Oscillation parameter values
Parameter
Values
Default
Input osc. level
2...50 events/s
30 events/s
Input osc. hyst
2...50 events/s
10 events/s
3.10
Binary outputs
The protection relay provides a number of binary outputs used for tripping, executing
local or remote control actions of a breaker or a disconnector, and for connecting the
Section 3
1MRS240050-IB C
Basic functions
76
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...