32P executes on the direction of positive-sequence power and not the
value. If overpower or underpower is needed, refer to 32O and 32U. 32P
is generally used for directional controls.
4.4.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 32P can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
Directional
detector
V1
I1
BLOCK
RELEASE
Blocking
logic
t
Timer
Low level
blocking
DIRECTION
GUID-D45D62FF-12ED-47FA-9B97-FF5BF0251AFE-ANSI V1 EN
Figure 133:
Functional module diagram
Directional detector
The Directional detector module compares the angle of the positive-sequence current I1
to the angle of the positive-sequence voltage V1. Using the positive-sequence voltage
angle as reference, the positive-sequence current angle is compared to the
Characteristic
angle
setting. If the angular difference is within the operating sector selected with the
Directional mode
setting, the Enable signal is sent to Timer.
The operating sector is defined by the setting
Min forward angle
,
Max forward angle
,
Min
reverse angle
and
Max reverse angle
. The options that can be selected for the
Directional
mode
setting are “Forward” and “Reverse”.
1MRS240050-IB C
Section 4
Protection functions
REF615R
283
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...