5.2.6
Signals
Table 254:
50BF Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
I_N
SIGNAL
0
Ground current
BLOCK
BOOLEAN
0=False
Block CBFP operation
PICKUP
BOOLEAN
0=False
CBFP pickup command
POSCLOSE
BOOLEAN
0=False
CB in closed position
CB_FAULT
BOOLEAN
0=False
CB faulty and unable to trip
Table 255:
50BF Output signals
Name
Type
Description
CB_FAULT_AL
BOOLEAN
Delayed CB failure alarm
TRBU
BOOLEAN
Backup trip
TRRET
BOOLEAN
Retrip
5.2.7
Settings
Table 256:
50BF Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Current value
0.05...1.00
xIn
0.05
0.30
Operating phase current
Current value Res
0.05...1.00
xIn
0.05
0.30
Operating residual current
CB failure trip mode
1=2 out of 4
2=1 out of 3
3=1 out of 4
1=2 out of 4
Backup trip current check mode
CB failure mode
1=Current
2=Breaker status
3=Both
1=Current
Operating mode of function
CB fail retrip mode
1=Disabled
2=Without Check
3=Current check
1=Disabled
Operating mode of retrip logic
Retrip time
0...60000
ms
10
20
Delay timer for retrip
CB failure delay
0...60000
ms
10
150
Delay timer for backup trip
Table continues on next page
1MRS240050-IB C
Section 5
Protection-related functions
REF615R
327
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...