A070864 V3 EN
Figure 237:
Functional module diagram
9.2.4.1
Signal collection and delay logic
When the protection trips, the initiation of autoreclosing shots is in most applications
executed with the
INIT_1...6
inputs. The
DEL_INIT2...4
inputs are not used. In
some countries, pickup of the protection stage is also used for the shot initiation. This is
the only time when the
DEL_INIT
inputs are used.
1MRS240050-IB C
Section 9
Control functions
REF615R
461
Technical Manual