The sag of overhead lines can reach an unacceptable value.
•
If the temperature of conductors, for example aluminium conductors, becomes too
high, the material will be destroyed.
•
Overheating can damage the insulation on cables which in turn increases the risk of
phase-to-phase or phase-to-ground faults.
In stressed situations in the power system, the lines and cables may be required to be
overloaded for a limited time. This should be done without any risk for the above-
mentioned risks.
The thermal overload protection provides information that makes temporary overloading
of cables and lines possible. The thermal overload protection estimates the conductor
temperature continuously. This estimation is made by using a thermal model of the line/
cable that is based on the current measurement.
If the temperature of the protected object reaches a set warning level, a signal is given to
the operator. This enables actions in the power system to be done before dangerous
temperatures are reached. If the temperature continues to increase to the maximum
allowed temperature value, the protection initiates a trip of the protected line.
4.5.1.6
Signals
Table 236:
49F Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for trip outputs
ENA_MULT
BOOLEAN
0=False
Enable Current multiplier
TEMP_AMB
FLOAT32
0
The ambient temperature used in the calculation
Table 237:
49F Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
ALARM
BOOLEAN
Thermal Alarm
BLK_CLOSE
BOOLEAN
Thermal overload indicator. To inhibite reclose.
1MRS240050-IB C
Section 4
Protection functions
REF615R
299
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...