Table 362:
Interlocking conditions for enabling the closing (opening) command
Inputs
Outputs
INT_BYPASS
ENA_CLOSE
(ENA_OPEN)
BLK_CLOSE
(BLK_OPEN)
CLOSE_ENAD
(OPEN_ENAD)
0 = False
0 = False
0 = False
0 = False
0 = False
0 = False
1 = True
0 = False
0 = False
1 = True
0 = False
1 = True
0 = False
1 = True
1 = True
0 = False
1 = True
0 = False
0 = False
1 = True
1 = True
0 = False
1 = True
0 = False
1 = True
1 = True
0 = False
1 = True
1 = True
1 = True
1 = True
0 = False
Opening and closing operations
The opening and closing operations are available via communication, binary inputs or
LHMI commands. As a prerequisite for control commands, there are enabling and
blocking functionalities for both opening and closing commands (
CLOSE_ENAD
and
OPEN_ENAD
signals). If the control command is executed against the blocking or if the
enabling of the corresponding command is not valid, 52 generates an error message.
Opening and closing pulse widths
The pulse width type can be defined with the
Adaptive pulse
setting. The function provides
two modes to characterize the opening and closing pulse widths. When the
Adaptive pulse
is set to “TRUE”, it causes a variable pulse width, which means that the output pulse is
deactivated when the object state shows that the apparatus has entered the correct state. If
apparatus fails to enter the correct state, the output pulse is deactivated after the set
Operation timeout
setting, and an error message is displayed. When the
Adaptive pulse
is
set to “FALSE”, the functions always use the maximum pulse width, defined by the user-
configurable
Pulse length
setting. The
Pulse length
setting is the same for both the
opening and closing commands. When the apparatus already is in the right position, the
maximum pulse length is given.
The
Pulse length
setting does not affect the length of the trip pulse.
Control methods
The command execution mode can be set with the
Control model
setting. The alternatives
for command execution are direct control and secured object control, which can be used
to secure controlling.
1MRS240050-IB C
Section 9
Control functions
REF615R
453
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...