Table 227:
32P Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Reset delay time
0...60000
ms
1
20
Reset delay time
Min trip current
0.01...1.00
xIn
0.01
0.10
Minimum trip current
Min trip voltage
0.01...1.00
xUn
0.01
0.30
Minimum trip voltage
4.4.1.8
Monitored data
Table 228:
32P Monitored data
Name
Type
Values (Range)
Unit
Description
ANGLE_RCA
FLOAT32
-180.00...180.00
deg
Angle between polarizing and
operating quantity
32P
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.4.2
Ground directional power protection 32N
4.4.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Ground directional power protection
DNZSRDIR
I2->, Io->
32N
4.4.2.2
Function block
GUID-DCCE78B9-9984-4C66-A320-7C6F89243C3A-ANSI V1 EN
Figure 135:
Function block
Section 4
1MRS240050-IB C
Protection functions
286
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...