The trip times for the ANSI and IEC IDMT curves are defined with the coefficients A, B
and C.
The values of the coefficients can be calculated according to the formula:
t s
A
I
I
B
k
c
[ ]
=
>
−
+
⋅
1
A060821 V2 EN
(Equation 33)
t[s] t[s] = Trip time in seconds
I
measured current
I>
set
Pickup value
k
set
Time multiplier
Table 438:
Curve parameters for ANSI and IEC IDMT curves
Curve name
A
B
C
(1) ANSI Extremely
Inverse
28.2
0.1217
2.0
(2) ANSI Very Inverse
19.61
0.491
2.0
(3) ANSI Normal Inverse
0.0086
0.0185
0.02
(4) ANSI Moderately
Inverse
0.0515
0.1140
0.02
(6) Long Time Extremely
Inverse
64.07
0.250
2.0
(7) Long Time Very
Inverse
28.55
0.712
2.0
(8) Long Time Inverse
0.086
0.185
0.02
(9) IEC Normal Inverse
0.14
0.0
0.02
(10) IEC Very Inverse
13.5
0.0
1.0
(11) IEC Inverse
0.14
0.0
0.02
(12) IEC Extremely
Inverse
80.0
0.0
2.0
(13) IEC Short Time
Inverse
0.05
0.0
0.04
(14) IEC Long Time
Inverse
120
0.0
1.0
1MRS240050-IB C
Section 12
General function block features
REF615R
577
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...