If the circuit breaker is manually closed against the fault, that is, if SOTF is used, the fourth
time delay can automatically be taken into use. This is controlled with the internal logic
of the AR function and the
Fourth delay in SOTF
parameter.
A typical autoreclose situation is where one autoreclosing shot has been performed after
the fault was detected. There are two types of such cases: operation initiated with
protection pickup signal and operation initiated with protection trip signal. In both cases,
the autoreclosing sequence is successful: the reclaim time elapses and no new sequence is
picked up.
A070867 V1 EN
Figure 240:
Signal scheme of autoreclosing operation initiated with protection pickup
signal
The autoreclosing shot is initiated with a trip signal of the protection function after the
pickup delay time has elapsed. The autoreclosing picks up when the
Str 2 delay shot 1
setting elapses.
A070868-ANSI V1 EN
Figure 241:
Signal scheme of autoreclosing operation initiated with protection trip
signal
Section 9
1MRS240050-IB C
Control functions
464
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...