Blocking logic
The binary input
BLOCK
can be used to block the function. The activation of the
BLOCK
input deactivates the
RELEASE
output and resets Timer.
4.4.1.5
Application
The three-phase directional power protection 32P improves the possibility to obtain a
selective function of the overcurrent protection in meshed networks. The function is used
to block or release other overcurrent protection functions.
4.4.1.6
Signals
Table 224:
32P Input signals
Name
Type
Default
Description
V1
REAL
0.0
Positive sequence voltage
I1
REAL
0.0
Positive sequence current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 225:
32P Output signals
Name
Type
Description
RELEASE
BOOLEAN
direction signal
DIRECTION
Enum
Direction information
4.4.1.7
Settings
Table 226:
32P Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Release delay time
0...1000
ms
1
10
Release delay time
Characteristic angle
-179...180
deg
1
60
Characteristic angle
Max forward angle
0...90
deg
1
88
Maximum phase angle in forward direction
Max reverse angle
0...90
deg
1
88
Maximum phase angle in reverse direction
Min forward angle
0...90
deg
1
88
Minimum phase angle in forward direction
Min reverse angle
0...90
deg
1
88
Minimum phase angle in reverse direction
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
1MRS240050-IB C
Section 4
Protection functions
REF615R
285
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...