60 Hz
Pickup value Freq
set at 0.975 xFn
Pickup value df/dt
set at -0.020 xFn/s
Trip Tm df/dt
= 500ms
Trip Tm Freq
= 1000ms
Load shed mode
= Freq< AND df/dt
58.8 Hz
ST_FRG
OPR_FRG
500ms
1s
TRIP is not activated
in this case as Freq<
condition not satisfied
TRIP
Start of operation timer
Time [s]
Frequency
[Hz]
GUID-DD22BDCD-1B89-4370-81D2-8F032EE4C08A V3 EN
Figure 130:
Load-shedding operation in the “Freq< AND df/dt>” mode when only the
df/dt condition is satisfied (Rated frequency=60 Hz)
Restore detection
If after the activation of the
TRIP
input the frequency recovers to a level above the
Restore
pickup Val
setting, the
RESTORE
signal output is activated. The
RESTORE
output
remains active for a 100 ms. The
Restore mode
setting is used to select the restoring mode
to be "Disabled", "Auto" or "Manual".
1MRS240050-IB C
Section 4
Protection functions
REF615R
275
Technical Manual