, the corresponding limits regarding the swell operation are provided with
the inherent magnitude limit order difference. The swell functionality principle is the
same as for dips, but the different limits for the signal magnitude and times and the
inherent operating zone change (here,
Voltage swell set x
> 1.0 xVn) are applied.
Voltage swell set 3
Voltage swell set 2
Voltage swell set 1
Voltage
xVref
Time (ms)
0
0
VVa Dur Max
VVa swell time 3
VVa swell time 1
VVa swell time 2
1.40
Instantaneous
swell
Temporary
swell
Momentary
swell
Maximum duration
swell
1.00
GUID-C1C6BEEF-439A-4DF7-8065-5F88C7517834-ANSI V1 EN
Figure 221:
Voltage swell operational regions
For interruption, as shown in
, there is only one magnitude limit but four
duration limits for interruption classification. Now the event and counter type depends
only on variation duration time.
Voltage Int set
Voltage
xVref
Time (ms)
0
0
VVa Dur Max
VVa Int time 3
VVa Int time 1
VVa Int time 2
1.00
Momentary
interruption
Sustained
interruption
Temporary
interruption
Maximum duration
interruption
GUID-0204C8EA-102C-4327-BE84-DCE27747AA30-ANSI V1 EN
Figure 222:
Interruption operating regions
1MRS240050-IB C
Section 8
Power quality measurement functions
REF615R
425
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...