data and a new variation is detected, the latest data set is placed into bank 1 and the data
in bank 3 is overwritten by the data from bank 2.
The recorded data can be reset with the
RESET
binary input signal by navigating to the
HMI reset (
Main menu/Clear/Reset recorded data/PQVUBx
) or through tools via
communications.
When voltage unbalance is detected in the system, PQVUB responds with the
MN_UNB_AL
alarm signal. During the alarm situation, PQVUB stores the maximum
magnitude and the time of occurrence and the duration of alarm
MN_UNB_AL
. The
recorded data is stored when
MN_UNB_AL
is deactivated.
Table 355:
Recorded data
Parameter
Description
Alarm high mean Dur
Time duration for alarm high mean unbalance
Max unbalance Volt
Maximum three-second voltage
Time Max Unb Volt
Time stamp of voltage unbalance
8.4.5
Application
Voltage unbalance is one of the basic power quality parameters.
Ideally, in a three-phase or multiphase power system, the frequency and voltage
magnitude of all the phases are equal and the phase displacement between any two
consecutive phases is also equal. This is called a balanced source. Apart from the balanced
source, usually the power system network and loads are also balanced, implying that
network impedance and load impedance in each phase are equal. In some cases, the
condition of a balance network and load is not met completely, which leads to a current
and voltage unbalance in the system. Providing unbalanced supply voltage has a
detrimental effect on load operation. For example, a small magnitude of a negative-
sequence voltage applied to an induction motor results in a significant heating of the
motor.
A balanced supply, balanced network and balanced load lead to a better power quality.
When one of these conditions is disturbed, the power quality is deteriorated. PQVUB
monitors such voltage unbalance conditions in power transmission and distribution
networks. PQVUB calculates two sets of measured values, a three-second and a ten-
minute non-sliding average value. The three-second average value is used for continuous
monitoring while the ten-minute average value is used for percentile calculation for a
longer period of time. It can be applied to identify the network and load unbalance that
may cause sustained voltage unbalance. A single-phase or phase-to-phase fault in the
network or load side can create voltage unbalance but, as faults are usually isolated in a
1MRS240050-IB C
Section 8
Power quality measurement functions
REF615R
445
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...