For a more detailed description of the IDMT curves and the use of the
Curve Sat Relative
IDMT curve saturation of the over
section in this manual.
Phase selection logic
If the fault criteria are fulfilled in the level detector, the phase selection logic detects the
phase or phases in which the fault level is detected. If the number of faulty phases match
with the set
Num of pickup phases
, the phase selection logic activates the Timer.
Timer
Once activated, the Timer activates the
PICKUP
output. Depending on the value of the set
Operating curve type
, the time characteristics are selected according to DT or IDMT.
For a detailed description of the voltage IDMT curves, see the
curves for overvoltage protection
section in this manual.
When the operation timer has reached the value set by
Trip delay time
in the DT mode or
the maximum value defined by the IDMT, the
TRIP
output is activated.
When the user-programmable IDMT curve is selected, the trip time characteristics are
defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation occurs, that is, a fault suddenly disappears before the trip delay is
exceeded, the reset state is activated. The behavior in the drop-off situation depends on the
selected trip time characteristics. If the DT characteristics are selected, the reset timer runs
until the set
Reset delay time
value is exceeded. If the drop-off situation exceeds the set
Reset delay time
, the Timer is reset and the
PICKUP
output is deactivated.
When the IDMT operate time curve is selected, the functionality of the Timer in the drop-
off state depends on the combination of the
Type of reset curve
and
Reset delay time
settings.
Table 171:
The reset time functionality when the IDMT trip time curve is selected
Type of reset curve
Description of operation
“Immediate”
The trip timer is reset instantaneously when drop-off
occurs.
“Def time reset”
The trip timer is frozen during drop-off. The trip timer
is reset after the set
Reset delay time is exceeded.
“DT Lin decr rst”
The trip timer value linearly decreases during the
drop-off situation. The trip timer is reset after the set
Reset delay time is exceeded.
Section 4
1MRS240050-IB C
Protection functions
224
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...