The delayed inverse-time reset is not available for IEC-type inverse time
curves.
User-programmable delayed inverse reset
The user can define the delayed inverse reset time characteristics with the following
formula using the set
Curve parameter D
.
t s
D
I
I
k
[ ]
=
>
−
⋅
2
1
A060817 V3 EN
(Equation 38)
t[s] Reset time (in seconds)
k
set
Time multiplier
D
set
Curve parameter D
I
Measured current
I>
set
Pickup value
12.2.3
Inverse-timer freezing
When the
BLOCK
input is active, the internal value of the time counter is frozen at the
value of the moment just before the freezing. Freezing of the counter value is chosen when
the user does not wish the counter value to count upwards or to be reset. This may be the
case, for example, when the inverse-time function of a protection relay needs to be
blocked to enable the definite-time operation of another protection relay for selectivity
reasons, especially if different relaying techniques (old and modern relays) are applied.
The selected blocking mode is "Freeze timer".
The activation of the
BLOCK
input also lengthens the minimum delay
value of the timer.
Section 12
1MRS240050-IB C
General function block features
604
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...