Control and status indication facilities are implemented in the same package with 52.
When primary components are controlled in the energizing phase, for example, the correct
execution sequence of the control commands must be ensured. This can be achieved, for
example, with interlocking based on the status indication of the related primary
components. The interlocking on substation level can be applied using the IEC 61850
GOOSE messages between feeders.
REF615R
REF615R
REF615R
REF615R
Control and interlocking via GOOSE messages
52-2
52-3
52-4
52-1
GUID-750C4C62-7E10-42D8-AECF-098EBEA748C4 V1 EN
Figure 234:
Status indication-based interlocking via the GOOSE messaging
9.1.6
Signals
Table 363:
52 Input signals
Name
Type
Default
Description
ENA_OPEN
BOOLEAN
1=True
Enables opening
ENA_CLOSE
BOOLEAN
1=True
Enables closing
BLK_OPEN
BOOLEAN
0=False
Blocks opening
BLK_CLOSE
BOOLEAN
0=False
Blocks closing
ITL_BYPASS
BOOLEAN
0=False
Discards ENA_OPEN and ENA_CLOSE interlocking
when TRUE
AU_OPEN
BOOLEAN
0=False
Input signal used to open the breaker
1)
AU_CLOSE
BOOLEAN
0=False
Input signal used to close the breaker
1)
POSOPEN
BOOLEAN
0=False
Signal for open position of apparatus from I/O
1)
POSCLOSE
BOOLEAN
0=False
Signal for closed position of apparatus from I/O
1)
1) Not available for monitoring
1MRS240050-IB C
Section 9
Control functions
REF615R
455
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...