RCA
= 0 deg
Non-operating area
Min forward angle
Min reverse angle
Min operate
current
Max forward angle
Max reverse angle
Forward
area
Backward
area
0
-V
0
I
GUID-92004AD5-05AA-4306-9574-9ED8D51524B4-ANSI V1 EN
Figure 88:
Configurable operating sectors in phase angle characteristic
Table 139:
Momentary operating direction
Fault direction
The value for DIRECTION
Angle between the polarizing and operating quantity
is not in any of the defined sectors.
0 = unknown
Angle between the polarizing and operating quantity
is in the forward sector.
1= forward
Angle between the polarizing and operating quantity
is in the reverse sector.
2 = backward
Angle between the polarizing and operating quantity
is in both the forward and the reverse sectors, that is,
the sectors are overlapping.
3 = both
Section 4
1MRS240050-IB C
Protection functions
186
REF615R
Technical Manual