Table 390:
Non-group analog channel settings for digital fault recorder
Parameter
Values (Range) Unit
Step
Default
Description
Operation
1=Enable
5=Disable
1
1=Enable for
Channel 1
5=Disable for
channels 2 - 8
Analog
channel is
enabled or
disabled
Channel
selection
0=Disabled
1=IG-A
2=IA-A
3=IB-A
4=IC-A
9=VG
10=VA
11=VB
12=VC
14=VSync
17=3I0
18=I1-A
1)
19=I2-A
1)
20=V0
21=V1
1)
22=V2
1)
29=VAB
30=VBC
31=VCA
0
2)
Select the
signal to be
recorded by
this channel.
Applicable
values for this
parameter are
product variant
dependent.
Every product
variant
includes only
the values that
are applicable
to that
particular
variant
Channel id text
0 to 64
characters,
alphanumeric
DR analog
channel X
Identification
text for the
analog channel
used in the
COMTRADE
format
High trigger
level
0.00...60.00
pu
0.01
10.00
High trigger
level for the
analog channel
Low trigger
level
0.00...2.00
pu
0.01
0.00
Low trigger
level for the
analog channel
Storage mode
0=Waveform
1=Trend / cycle
1
0
Storage mode
for the analog
channel
1) Recordable values are available only in trend mode. In waveform mode, samples for this signal type are
constant zeroes. However, these signal types can be used to trigger the recorder on limit violations of the
corresponding analog channel.
2) Refer to the application manual for channel allocation for each configuration.
Section 10
1MRS240050-IB C
Recording functions
524
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...