9.3.6
Signals
Table 378:
25 Input signals
Name
Type
Default
Description
V_BUS
SIGNAL
0=False
Busbar Voltage
V_LINE
SIGNAL
0=False
Line Voltage
BLOCK
BOOLEAN
0=False
Blocking signal of the synchro check and voltage check
function
CL_COMMAND
BOOLEAN
0=False
External closing request
BYPASS
BOOLEAN
0=False
Request to bypass synchronism check and voltage
check
Table 379:
25 Output signals
Name
Type
Description
SYNC_INPRO
BOOLEAN
Synchronizing in progress
SYNC_OK
BOOLEAN
Systems in synchronism
CL_FAIL_AL
BOOLEAN
CB closing failed
CMD_FAIL_AL
BOOLEAN
CB closing request failed
LLDB
BOOLEAN
Live Line, Dead Bus
LLLB
BOOLEAN
Live Line, Live Bus
DLLB
BOOLEAN
Dead Line, Live Bus
DLDB
BOOLEAN
Dead Line, Dead Bus
9.3.7
Settings
Table 380:
25 Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Live dead mode
-1=Off
1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live
1=Both Dead
Energizing check mode
Difference voltage
0.01...0.50
xUn
0.01
0.05
Maximum voltage difference limit
Difference frequency
0.001...0.100
xFn
0.001
0.001
Maximum frequency difference limit
Difference angle
5...90
deg
1
5
Maximum angle difference limit
Section 9
1MRS240050-IB C
Control functions
508
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...