4.1.8.7
Settings
Table 161:
46PD Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
10...100
%
1
10
Pickup value
Trip delay time
100...30000
ms
1
100
Trip delay time
Table 162:
46PD Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Reset delay time
0...60000
ms
1
20
Reset delay time
Min phase current
0.05...0.30
xIn
0.01
0.10
Minimum phase current
4.1.8.8
Monitored data
Table 163:
46PD Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
RATIO_I2_I1
FLOAT32
0.00...999.99
%
Measured current ratio I2 / I1
46PD
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.1.8.9
Technical data
Table 164:
46PD Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
±2% of the set value
Pickup time
<70 ms
Reset time
<40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1MRS240050-IB C
Section 4
Protection functions
REF615R
217
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...