5.5.7
Settings
Table 271:
AFD Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Phase pickup value
0.50...40.00
xIn
0.01
2.50
Operating phase current
Ground pickup value
0.05...8.00
xIn
0.01
0.20
Operating residual current
Operation mode
1=Light+current
2=Light only
3=BI controlled
1=Light+current
Operation mode
Table 272:
AFD Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
5.5.8
Monitored data
Table 273:
AFD Monitored data
Name
Type
Values (Range)
Unit
Description
AFD
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
5.5.9
Technical data
Table 274:
AFD Technical data
Characteristic
Value
Operation accuracy
±3% of the set value or ±0.01 × I
n
Trip time
Minimum
Typical
Maximum
Operation mode = "Light
only"
9 ms
10 ms
12 ms
Reset time
<40 ms
Reset ratio
Typically 0.96
Section 5
1MRS240050-IB C
Protection-related functions
344
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...