8.3.4.3
Variation validation
The validation criterion for voltage variation is that the measured total variation duration
is between the set minimum and maximum durations (Either one of
VVa dip time 1
,
VVa
swell time 1
or
VVa Int time 1
, depending on the variation type, and
VVa Dur Max
). The
maximum variation duration setting is the same for all variation types.
shows voltage dip operational regions. In
, only one voltage dip/
swell/Int set is drawn, whereas in this figure there are three sub-limits for the dip
operation. When
Voltage dip set 3
is undershot, the corresponding
PICKUP_x
and also
the
DIPST
outputs are activated. When the TRMS voltage magnitude remains between
Voltage dip set 2
and
Voltage dip set 1
for a period longer than
VVa dip time 2
(shorter time
than
VVa dip time 3
), a momentary dip event is detected. Furthermore, if the signal
magnitude stays between the limits longer than
VVa dip time 3
(shorter time than
VVa Dur
max
), a temporary dip event is detected. If the voltage remains below
Voltage dip set 1
for
a period longer than
VVa dip time 1
but a shorter time than
VVa dip time 2
, an
instantaneous dip event is detected.
For an event detection, the
TRIP
output is always activated for one task cycle. The
corresponding counter and only one of them (INSTDIPCNT, MOMDIPCNT or
TEMPDIPCNT) is increased by one. If the dip limit undershooting duration is shorter than
VVa dip time 1
,
VVa swell time 1
or
VVa Int time 1
, the event is not detected at all, and if
the duration is longer than
VVa Dur Max
, MAXDURDIPCNT is increased by one but no
event detection resulting in the activation of the
TRIP
output and recording data update
takes place. These counters are available through the monitored data view on the LHMI
or through tools via communications. There are no phase-segregated counters but all the
variation detections are registered to a common time/magnitude-classified counter type.
Consequently, a simultaneous multiphase event, that is, the variation-type event detection
time moment is exactly the same for two or more phases, is counted only once also for
single-phase power systems.
GUID-0D3F6D81-F905-4D8D-A579-836EF7BB6773-ANSI V1 EN
Figure 220:
Voltage dip operational regions
Section 8
1MRS240050-IB C
Power quality measurement functions
424
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...