Directional Coef
B
A
I
I
f
r
=
= −
log
log
.
2 2609
A070794 V2 EN
(Equation 19)
I
r
Rated operating current = 630 A
I
f
Rated fault current = 16 kA
A
Op number rated = 30000
B
Op number fault = 20
Calculation for estimating the remaining life
shows that there are 30,000 possible operations at the rated operating current
of 630 A and 20 operations at the rated fault current 16 kA. Therefore, if the tripping
current is 10 kA, one operation at 10 kA is equivalent to 30,000/60=500 operations at the
rated current. It is also assumed that prior to this tripping, the remaining life of the circuit
breaker is 15,000 operations. Therefore, after one operation of 10 kA, the remaining life
of the circuit breaker is 15,000-500=14,500 at the rated operating current.
Spring-charged indication
For normal operation of the circuit breaker, the circuit breaker spring should be charged
within a specified time. Therefore, detecting long spring-charging time indicates that it is
time for the circuit breaker maintenance. The last value of the spring-charging time can be
used as a service value.
Gas pressure supervision
The gas pressure supervision monitors the gas pressure inside the arc chamber. When the
pressure becomes too low compared to the required value, the circuit breaker operations
are locked. A binary input is available based on the pressure levels in the function, and
alarms are generated based on these inputs.
6.1.6
Signals
Table 275:
52CM Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block input status
Table continues on next page
Section 6
1MRS240050-IB C
Supervision functions
358
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...