7.1.6.3
Signals
Table 310:
IG Input signals
Name
Type
Default
Description
IG
SIGNAL
0
Ground current
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
Table 311:
IG Output signals
Name
Type
Description
HIGH_ALARM
BOOLEAN
High alarm
HIGH_WARN
BOOLEAN
High warning
7.1.6.4
Settings
Table 312:
IG Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
A Hi high limit res
0.00...40.00
xIn
0.20
High alarm current limit
A high limit res
0.00...40.00
xIn
0.05
High warning current limit
A deadband res
100...100000
2500
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
7.1.6.5
Monitored data
Table 313:
IG Monitored data
Name
Type
Values (Range)
Unit
Description
IG-A
FLOAT32
0.00...40.00
xIn
Measured residual current
Max demand IG
FLOAT32
0.00...40.00
xIn
Maximum demand for residual
current
Min demand IG
FLOAT32
0.00...40.00
xIn
Minimum demand for residual
current
Time max demand IG Timestamp
Time of maximum demand
residual current
Time min demand IG Timestamp
Time of minimum demand
residual current
Section 7
1MRS240050-IB C
Measurement functions
398
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...