8.4.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of PQVUB can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
BLOCK
Voltage
unbalance
detector
MN_UNB_AL
PCT_UNB_AL
OBS_PR_ACT
Percentile
calculation
Recorded
data
V_A
V_B
V_C
Average
calculation
V
1
V
2
V
0
GUID-69B09FFB-8F8F-49AE-BEC7-42CB7272C224 V1 EN
Figure 229:
Functional module diagram
Average calculation
PQVUB calculates two sets of measured voltage unbalance values, a three-second and a
ten-minute non-sliding average value. The three-second average value is used for
continuous monitoring. The ten-minute average is used for percentile calculation for a
longer period.
The Average calculation module uses five different methods for the average calculation.
The required method can be selected with the
Unb detection method
parameter.
When the "Neg Seq" mode is selected with
Unb detection method
, the voltage unbalance
is calculated based on the negative-sequence voltage magnitude. Similarly, when the
"Zero Seq" mode is selected, the voltage unbalance is calculated based on the zero-
sequence voltage magnitude. When the "Neg to Pos Seq" mode is selected, the voltage
unbalance is calculated based on the ratio of the negative-sequence voltage magnitude to
the positive-sequence magnitude. When the "Zero to Pos Seq" mode is selected, the
voltage unbalance is calculated based on the ratio of the zero-sequence voltage magnitude
to the positive-sequence magnitude. When the "Ph vectors Comp" mode is selected, the
ratio of the maximum phase voltage magnitude deviation from the mean voltage
magnitude to the mean of the phase voltage magnitude is used for voltage unbalance
calculation.
The calculated three-second value and ten-minute value are available in the Monitored
data view through the outputs
3S_MN_UNB
and
10MN_MN_UNB
.
1MRS240050-IB C
Section 8
Power quality measurement functions
REF615R
441
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...