occurs within the trip time up counting, the reset timer is activated. If the drop-off time
exceeds
Reset delay time
, the operation timer is reset.
The
BLOCK
input can be controlled with a binary input, a horizontal communication input
or an internal signal of the relay program. The activation of the
BLOCK
input prevents the
BLK2H
output from being activated.
It is recommended to use the second harmonic and the waveform based
inrush blocking from the 87T function, if available.
5.1.5
Application
Transformer protections require high stability to avoid tripping during magnetizing inrush
conditions. A typical example of an inrush detector application is doubling the pickup
value of an overcurrent protection during inrush detection.
The inrush detection function can be used to selectively block overcurrent and ground-
fault function stages when the ratio of second harmonic component over the fundamental
component exceeds the set value.
Other applications of this function include the detection of inrush in lines connected to a
transformer.
1MRS240050-IB C
Section 5
Protection-related functions
REF615R
315
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...