4.1.7.2
Function block
A070758-ANSI V1 EN
Figure 99:
Function block
4.1.7.3
Functionality
The negative-sequence overcurrent protection function 46 is used for increasing
sensitivity to detect single-phase and phase-to-phase faults or unbalanced loads due to, for
example, broken conductors or unsymmetrical feeder voltages.
46 can also be used for detecting broken conductors.
The function is based on the measurement of the negative sequence current. In a fault
situation, the function picks up when the negative sequence current exceeds the set limit.
The trip time characteristics can be selected to be either definite time (DT) or inverse
definite minimum time (IDMT). In the DT mode, the function trips after a predefined trip
time and resets when the fault current disappears. The IDMT mode provides current-
dependent timer characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
timers or the function itself, if desired.
4.1.7.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 46 can be described using a module diagram. All the modules in the
diagram are explained in the next sections.
1MRS240050-IB C
Section 4
Protection functions
REF615R
207
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...