6.1.7
Settings
Table 277:
52CM Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Acc stop current
5.00...500.00
A
0.01
10.00
RMS current setting below which engy acm
stops
Open alarm time
0...200
ms
1
40
Alarm level setting for open travel time in ms
Close alarm time
0...200
ms
1
40
Alarm level Setting for close travel time in ms
Opening time Cor
0...100
ms
1
10
Correction factor for open travel time in ms
Closing time Cor
0...100
ms
1
10
Correction factor for CB close travel time in ms
Spring charge time
0...60000
ms
10
1000
Setting of alarm for spring charging time of CB
in ms
Counter initial Val
0...9999
1
0
The operation numbers counter initialization
value
Alarm Op number
0...9999
1
200
Alarm limit for number of operations
Lockout Op number
0...9999
1
300
Lock out limit for number of operations
Current exponent
0.00...2.00
0.01
2.00
Current exponent setting for energy calculation
Difference Cor time
-10...10
ms
1
5
Corr. factor for time dif in aux. and main
contacts open time
Alm Acc currents Pwr
0.00...20000.00
0.01
2500.00
Setting of alarm level for accumulated currents
power
LO Acc currents Pwr
0.00...20000.00
0.01
2500.00
Lockout limit setting for accumulated currents
power
Ini Acc currents Pwr
0.00...20000.00
0.01
0.00
Initial value for accumulation energy (Iyt)
Directional Coef
-3.00...-0.50
0.01
-1.50
Directional coefficient for CB life calculation
Initial CB Rmn life
0...9999
1
5000
Initial value for the CB remaining life
Rated Op current
100.00...5000.00
A
0.01
1000.00
Rated operating current of the breaker
Rated fault current
500.00...75000.00
A
0.01
5000.00
Rated fault current of the breaker
Op number rated
1...99999
1
10000
Number of operations possible at rated current
Op number fault
1...10000
1
1000
Number of operations possible at rated fault
current
Life alarm level
0...99999
1
500
Alarm level for CB remaining life
Pressure alarm time
0...60000
ms
1
10
Time delay for gas pressure alarm in ms
Pres lockout time
0...60000
ms
10
10
Time delay for gas pressure lockout in ms
Inactive Alm days
0...9999
1
2000
Alarm limit value of the inactive days counter
Ini inactive days
0...9999
1
0
Initial value of the inactive days counter
Inactive Alm hours
0...23
h
1
0
Alarm time of the inactive days counter in hours
Section 6
1MRS240050-IB C
Supervision functions
360
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...