3.11.5
GOOSERCV_INTL function block
3.11.5.1
Function block
GUID-241A36E0-1BB9-4323-989F-39668A7B1DAC V1 EN
Figure 29:
Function block
3.11.5.2
Functionality
The GOOSERCV_INTL function is used to connect the GOOSE double binary input to
the application and extracting single binary position signals from the double binary
position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate state.
The default value (0) is used if VALID output indicates invalid status.
3.11.5.3
Signals
Table 42:
GOOSERCV_INTL Output signals
Name
Type
Description
POS_OP
BOOLEAN
Position open output signal
POS_CL
BOOLEAN
Position closed output signal
POS_OK
BOOLEAN
Position OK output signal
VALID
BOOLEAN
Output signal
1MRS240050-IB C
Section 3
Basic functions
REF615R
83
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...