Table 126:
50N/G-3 Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
1.00...40.00
xIn
0.01
1.00
Pickup value
Pickup value mult
0.8...10.0
0.1
1.0
Multiplier for scaling the pickup value
Trip delay time
20...200000
ms
10
20
Trip delay time
Table 127:
50N/G-3 Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Reset delay time
0...60000
ms
1
20
Reset delay time
IG/I0 signal Sel
1=Measured IG
2=Calculated I0
1=Measured IG
Measured IG or calculated I0
4.1.4.10
Monitored data
Table 128:
51N/G Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
51N/G
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Table 129:
50N/G-1/2 Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
50N/G-1/2
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Table 130:
50N/G-3 Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
EFIPTOC
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 4
1MRS240050-IB C
Protection functions
170
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...