Table 207:
Operation modes for operation logic
Operation mode
Description
Freq<
The function trips independently as the underfrequency ("Freq<")
protection function. When the measured frequency is below the set
value of the
Pickup value Freq< setting, the module activates the
PICKUP
and
PICKUP_UFRQ
outputs. The time characteristic is
according to DT. When the operation timer has reached the value set by
the
Trip Tm Freq setting, the
TRIP
and
TRIP_UFRQ
outputs are
activated. If the frequency restores before the module trips, the reset
timer is activated. If the timer reaches the value set by the
Reset delay
Tm Freq setting, the operation timer resets and the
PICKUP
and
PICKUP_UFRQ
outputs are deactivated.
Freq>
The function trips independently as the overfrequency ("Freq>")
protection function. When the measured frequency exceeds the set
value of the
Pickup value Freq> setting, the module activates the
PICKUP
and
PICKUP_OFRQ
outputs. The time characteristic is
according to DT. When the operation timer has reached the value set by
the
Trip Tm Freq setting, the
TRIP
and
TRIP_OFRQ
outputs are
activated. If the frequency restores before the module trips, the reset
timer is activated. If the timer reaches the value set by the
Reset delay
Tm Freq setting, the operation timer resets and the
PICKUP
and
PICKUP_OFRQ
outputs are deactivated.
df/dt
The function trips independently as the frequency gradient ("df/dt"),
rate-of-change, protection function. When the frequency gradient
exceeds the set value of the
Pickup value df/dt setting, the module
activates the
PICKUP
and
PICKUP_FRG
outputs. The time
characteristic is according to DT. When the operation timer has
reached the value set by the
Trip Tm df/dt setting, the
TRIP
and
TRIP_FRG
outputs are activated. If the frequency gradient restores
before the module trips, the reset timer is activated. If the timer reaches
the value set by the
Reset delay Tm df/dt setting, the operation timer
resets and the
PICKUP
and
PICKUP_FRG
outputs are deactivated.
Freq< + df/dt
A consecutive operation is enabled between the protection methods.
When the measured frequency is below the set value of the
Pickup
value Freq< setting, the frequency gradient protection is enabled. After
the frequency has dropped below the set value, the frequency gradient
is compared to the set value of the
Pickup value df/dt setting. When the
frequency gradient exceeds the set value, the module activates the
PICKUP
and
PICKUP_FRG
outputs. The time characteristic is
according to DT. When the operation timer has reached the value set by
the
Trip Tm df/dt setting, the
TRIP
and
TRIP_FRG
outputs are
activated. If the frequency gradient restores before the module trips, the
reset timer is activated. If the timer reaches the value set by the
Reset
delay Tm df/dt setting, the operation timer resets and the
PICKUP
and
PICKUP_FRG
outputs are deactivated. The
TRIP_UFRQ
output is not
active when this operation mode is used.
Table continues on next page
Section 4
1MRS240050-IB C
Protection functions
266
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...