In the “Freq<” mode, the measured frequency is compared to the set
Pickup value Freq<
.
If the measured value is lower than the set value of the
Pickup value Freq<
setting, the
module reports the value to the trip logic module.
df/dt detection
The frequency gradient detection module includes a detection for a positive or negative
rate-of-change (gradient) of frequency based on the set
Pickup value df/dt
value. The
negative rate-of-change protection is selected when the set value is negative. The positive
rate-of-change protection is selected when the set value is positive. When the frequency
gradient protection is selected and the gradient exceeds the set
Pickup value df/dt
value,
the module reports the exceeding of the value to the trip logic module.
The protection relay does not accept the set value "0.00" for the
Pickup
value df/dt
setting.
Operate logic
This module is used for combining different protection criteria based on the frequency and
the frequency gradient measurement to achieve a more sophisticated behavior of the
function. The criteria are selected with the
Operation mode
setting.
1MRS240050-IB C
Section 4
Protection functions
REF615R
265
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...