9.1.4
Operation principle
Status indication and validity check
The object state is defined by two digital inputs,
POSOPEN
and
POSCLOSE
, which are
also available as outputs
OPENPOS
and
CLOSEPOS
together with the
OKPOS
information. The debouncing and short disturbances in an input are eliminated by
filtering. The binary input filtering time can be adjusted separately for each digital input
used by the function block. The validity of the digital inputs that indicate the object state
is used as additional information in indications and event logging. The reporting of faulty
or intermediate position of the apparatus occurs after the
Event delay
setting, assuming
that the circuit breaker is still in a corresponding state.
Table 361:
Status indication
Status (POSITION)
POSOPEN/OPENPOS
POSCLOSE/
CLOSEPOS
OKPOS
1=Open
1=True
0=False
1=True
2=Closed
0=False
1=True
1=True
3=Faulty/Bad (11)
1=True
1=True
0=False
0=Intermediate (00)
0=False
0=False
0=False
Blocking
52 has a blocking functionality to prevent human errors that can cause serious injuries for
the operator and damages for the system components.
The basic principle for all blocking signals is that they affect the commands of other
clients: the operator place and protection and autoreclosing functions, for example. There
are two blocking principles.
•
Enabling the opening command: the function is used to block the operation of the
opening command. This block signal also affects the
OPEN
input of immediate
command.
•
Enabling the closing command: the function is used to block the operation of the
closing command. This block signal also affects the
CLOSE
input of immediate
command.
The
ITL_BYPASS
input is used if the interlocking functionality needs to be bypassed.
When
INT_BYPASS
is TRUE, the apparatus control is made possible by discarding the
ENA_OPEN
and
ENA_CLOSE
input states. However, the
BLK_OPEN
and
BLK_CLOSE
input signals are not bypassed with the interlocking bypass functionality since they always
have the higher priority.
Section 9
1MRS240050-IB C
Control functions
452
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...