4.5.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 49F can be described using a module diagram. All the modules in the
diagram are explained in the next sections.
A070747-ANSI V2 EN
Figure 142:
Functional module diagram
Max current selector
The max current selector of the function continuously checks the highest measured TRMS
phase current value. The selector reports the highest value to the temperature estimator.
Temperature estimator
The final temperature rise is calculated from the highest of the three-phase currents
according to the expression:
Θ
final
ref
ref
I
I
T
=
⋅
2
A070780 V2 EN
(Equation 12)
I
the largest phase current
I
ref
set
Current reference
T
ref
set
Temperature rise
The ambient temperature is added to the calculated final temperature rise estimation, and
the ambient temperature value used in the calculation is also available in the monitored
data as
TEMP_AMB
in degrees. If the final temperature estimation is larger than the set
Maximum temperature
, the
PICKUP
output is activated.
Current reference
and
Temperature raise
setting values are used in the final temperature
estimation together with the ambient temperature. It is suggested to set these values to the
Section 4
1MRS240050-IB C
Protection functions
296
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...