The
BLOCK
input blocks the
OBS_PR_ACT
output, which then disables the maximum
value calculation of the Statistics recorder module. If the trigger mode is selected
"Periodic" or "Continuous" and the blocking is deactivated before the next observation
period is due to start, the scheduled period starts normally.
Statistics recorder
The Statistics recorder module provides readily calculated three-second or ten-minute
values of the selected phase to the percentile calculator module based on the length of the
active observation period. If the observation period is less than one day, the three-second
average values are used. If the observation period is one day or longer, the ten-minute
average values are used.
The maximum three-second or ten-minute mean voltage unbalance is recorded during the
active observation period. The observation period start time
PR_STR_TIME
, observation
period end time
PR_END_TIME
, maximum voltage unbalance value during observation
period active,
MAX_UNB_VAL
and time of occurrence
MAX_UNB_TIME
are available
through the Monitored data view. These outputs are updated once
OBS_PR_ACT
deactivates.
Percentile calculator
The purpose of the Percentile calculator module is to find the voltage unbalance level so
that during the observation time 95 percent (default value of the
Percentile unbalance
setting) of all the measured voltage unbalance amplitudes are less than or equal to the
calculated percentile.
The computed output value
PCT_UNB_VAL
, below which the percentile of the values
lies, is available in the Monitored data view. The
PCT_UNB_VAL
output value is updated
at the end of the observation period.
If the output
PCT_UNB_VAL
is higher than the defined setting
Unbalance pickup val
at
the end of the observation period, an alarm output
PCT_UNB_AL
is activated. The
PCT_UNB_AL
output remains active for the whole period before the next period
completes.
The
BLOCK
input blocks the output
PCT_UNB_VAL
.
Recorded data
The information required for a later fault analysis is stored when the Recorded data
module is triggered. This happens when a voltage unbalance is detected by the Voltage
unbalance detector module.
Three sets of recorded data are available in total. The sets are saved in data banks 1...3. The
data bank 1 holds the most recent recorded data. Older data are moved to the subsequent
banks (1 to 2 and 2 to 3) when a voltage unbalance is detected. When all three banks have
Section 8
1MRS240050-IB C
Power quality measurement functions
444
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...