Activating the
BLOCK
input alone does not affect the operation of the
PICKUP
output. It
still becomes active when the current exceeds the set
Pickup value
, and inactive when the
current falls below the set
Pickup value
and the set
Reset delay time
has expired.
12.3
Voltage based inverse definite minimum time
characteristics
12.3.1
IDMT curves for overvoltage protection
In inverse-time modes, the trip time depends on the momentary value of the voltage, the
higher the voltage, the faster the trip time. The trip time calculation or integration starts
immediately when the voltage exceeds the set value of the
Pickup value
setting and the
PICKUP
output is activated.
The
TRIP
output of the component is activated when the cumulative sum of the integrator
calculating the overvoltage situation exceeds the value set by the inverse time mode. The
set value depends on the selected curve type and the setting values used. The user
determines the curve scaling with the
Time multiplier
setting.
The
Minimum trip time
setting defines the minimum trip time for the IDMT mode, that is,
it is possible to limit the IDMT based trip time for not becoming too short. For example:
1MRS240050-IB C
Section 12
General function block features
REF615R
605
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...