Operating curve type
51P
50P-1/2
(6) Long Time Extremely Inverse
x
(7) Long Time Very Inverse
x
(8) Long Time Inverse
x
(9) IEC Normal Inverse
x
x
(10) IEC Very Inverse
x
x
(11) IEC Inverse
x
(12) IEC Extremely Inverse
x
x
(13) IEC Short Time Inverse
x
(14) IEC Long Time Inverse
x
(15) IEC Definite Time
x
x
(17) User programmable
x
x
(18) RI type
x
(19) RD type
x
50P-3 supports only definite time characteristic.
For a detailed description of timers, see the
Table 69:
Reset time characteristics supported by different stages
Reset curve type
51P
50P-1/2
Note
(1) Immediate
x
x
Available for all reset time curves
(2) Def time reset
x
x
Available for all reset time curves
(3) Inverse reset
x
x
Available only for ANSI and user
programmable curves
The
Type of reset curve
setting does not apply to 50P-3 or when the DT
operation is selected. The reset is purely defined by the
Reset delay time
setting.
Section 4
1MRS240050-IB C
Protection functions
118
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...