Figure 84:
Definition of the relay characteristic angle, RCA=–90 degrees in an
isolated network
Directional ground-fault protection in an isolated neutral network
In isolated networks, there is no intentional connection between the system neutral point
and ground. The only connection is through the line-to-ground capacitances (C
0
) of
phases and leakage resistances (R
0
). This means that the zero-sequence current is mainly
capacitive and has a phase shift of -90 degrees compared to the residual voltage (-V
0
).
Consequently, the relay characteristic angle (RCA) should be set to -90 degrees and the
operation criteria to "IoSin" or "Phase angle". The width of the operating sector in the
phase angle criteria can be selected with the settings
Min forward angle
,
Max forward
angle
,
Min reverse angle
or
Max reverse angle
describes how the ground-fault
current is defined in isolated neutral networks.
For definitions of different directional ground-fault characteristics, see
Directional ground-fault principles
Section 4
1MRS240050-IB C
Protection functions
180
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...