-VG ( polarizing quantity)
Max forward
angle
Min forward
angle
Min reverse
angle
Non-operating area
IG ( operating quantity)
Max reverse
angle
Non-operating area
Characteristic angle/
Max torque line
Min trip voltage
Min trip current
RCA = 0 deg
Zero torque line
GUID-8BE1EAC6-FF7E-47F4-9333-A2E77917194F V1 EN
Figure 138:
Configurable directional setting for "Measured VG" or "Calculated VN"
(residual voltage) using Pol signal Sel setting
The
Characteristic angle
setting is done based on method of grounding employed in the
network. For example, in case of an isolated network,
Characteristic angle
is set to -90°,
and in case of a compensated network,
Characteristic angle
is set to 0° and 60° for solidly
grounded systems. In general
Characteristic angle
is selected so that it matches close to
the expected fault angle value, which results in maximum sensitivity.
Characteristic
angle
can be set anywhere between -179° to +180°. The figures show examples of the
operating area with RCA set to +60° and -90°, respectively.
Section 4
1MRS240050-IB C
Protection functions
290
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...