The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode, the
operation timer is frozen to the prevailing value, but the
TRIP
output is not deactivated
when blocking is activated. In the "Block all" mode, the whole function is blocked and the
timers are reset. In the "Block TRIP output" mode, the function operates normally but the
TRIP
output is not activated.
4.1.3.5
Measurement modes
The function operates on three alternative measurement modes: “RMS”, “DFT” and
“Peak-to-Peak” . The measurement mode is selected with the
Measurement mode
setting.
Table 96:
Measurement modes supported by 67/51P and 67/50P stages
Measurement mode
67/51P
67/50P-1 and 67/50P-2
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
4.1.3.6
Directional overcurrent characteristics
The forward and reverse sectors are defined separately. The forward operation area is
limited with the
Min forward angle
and
Max forward angle
settings. The reverse operation
area is limited with the
Min reverse angle
and
Max reverse angle
settings.
The sector limits are always given as positive degree values.
In the forward operation area, the
Max forward angle
setting gives the counterclockwise
sector and the
Min forward angle
setting gives the corresponding clockwise sector,
measured from the
Characteristic angle
setting.
In the backward operation area, the
Max reverse angle
setting gives the counterclockwise
sector and the
Min reverse angle
setting gives the corresponding clockwise sector, a
measurement from the
Characteristic angle
setting that has been rotated 180 degrees.
Relay characteristic angle (RCA) is set positive if the operating current lags the polarizing
quantity and negative if the operating current leads the polarizing quantity.
1MRS240050-IB C
Section 4
Protection functions
REF615R
143
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...