The frequent operation counter limit is reached and new sequence is initiated. The
lockout is released when the recovery timer elapses.
•
The protection trip signal has been active longer than the time set with the
Max wait
time
parameter since the shot initiation.
•
The circuit breaker is closed manually during an autoreclosing sequence and the
manual close mode is FALSE.
9.2.4.6
Protection coordination controller
The
PROT_CRD
output is used for controlling the protection functions. In several
applications, such as fuse-saving applications involving down-stream fuses, tripping and
initiation of shot 1 should be fast (instantaneous or short-time delayed). The tripping and
initiation of shots 2, 3 and definite tripping time should be delayed.
In this example, two overcurrent elements 51P and 50P-2 are used. 50P-2 is given an
instantaneous characteristic and 51P is given a time delay.
The
PROT_CRD
output is activated, if the
SHOT_PTR
value is higher than the value
defined with the
Protection crd limit
setting and all initialization signals have been reset.
The
PROT_CRD
output is reset under the following conditions:
•
If the cut-out time elapses
•
If the reclaim time elapses and the AR function is ready for a new sequence
•
If the AR function is in lockout or disabled, that is, if the value of the
Protection crd
mode
setting is "AR inoperative" or "AR inop, CB man".
The
PROT_CRD
output can also be controlled with the
Protection crd mode
setting. The
setting has the following modes:
•
"no condition": the
PROT_CRD
output is controlled only with the
Protection crd limit
setting
•
"AR inoperative": the
PROT_CRD
output is active, if the AR function is disabled or
in the lockout state, or if the
INHIBIT_RECL
input is active
•
"CB close manual": the
PROT_CRD
output is active for the reclaim time if the circuit
breaker has been manually closed, that is, the AR function has not issued a close
command
•
"AR inop, CB man": both the modes "AR inoperative" and "CB close manual" are
effective
•
"always": the
PROT_CRD
output is constantly active
1MRS240050-IB C
Section 9
Control functions
REF615R
473
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...