Directional operation is not allowed (the setting
Allow Non Dir
is "False") when the
measured polarizing or operating quantities are not valid, that is, their magnitude is below
the set minimum values. The minimum values can be defined with the settings
Min trip
current
and
Min trip voltage
. In case of low magnitudes, the
FAULT_DIR
and
DIRECTION
outputs are set to 0 = unknown, except when the
Allow non dir
setting is
"True". In that case, the function is allowed to operate in the directional mode as non-
directional, since the directional information is invalid.
The
RCA_CTL
input is used in compensated networks where the compensation coil
sometimes can be disconnected. When the coil is disconnected, the compensated network
becomes isolated and the
Characteristic angle
setting (φRCA) must be changed. This can
be done automatically with the
RCA_CTL
input. Note that the
RCA_CTL
input only works
when the
Characteristic angle
setting is set to exactly -90 degrees or 0 degrees. The value
of the input affects the
Characteristic angle
setting in the following way:
Table 140:
Characteristic angle control in phase angle operation mode
Characteristic angle setting
RCA_CTL
= "False"
RCA_CTL
= "True"
-90°
φRCA = -90°
φRCA = 0°
0°
φRCA = 0°
φRCA = -90°
Iosin(φ) and Iocos(φ) criteria
A more modern approach to directional protection is the active or reactive current
measurement. The operating characteristic of the directional operation depends on the
grounding principle of the network. The I
0
sin(φ) characteristics is used in an isolated
network, measuring the reactive component of the fault current caused by the ground
capacitance. The I
0
cos(φ) characteristics is used in a compensated network, measuring the
active component of the fault current.
The operation criteria Iosin(φ) and Iocos(φ) are selected with the
Operation mode
setting
using the values "IoSin" or "IoCos" respectively.
In isolated networks, I
0
sin(φ) does not differ from the phase angle criterion, since the
phase angle of the operating quantity is fairly close to -90 degrees. Furthermore, in
completely compensated networks the fault current is usually mostly resistive. Therefore,
the phase angle and I
0
cos(φ) criteria are equally sensitive. However, if the fault is in the
background network, the fault current of a sound and healthy line is almost fully
capacitive and its phase angle is close to the operation area of the component. Therefore,
the I
0
cos(φ) characteristic is recommended, since the risk of faulty operation is smaller
than with the phase angle criterion.
The angle correction setting can be used to improve selectivity. The setting decreases the
operation sector. The correction can only be used with the Iosin(φ) or Iocos(φ) criterion.
The
RCA_CTL
input is used to change the IG characteristic:
1MRS240050-IB C
Section 4
Protection functions
REF615R
187
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...