7.1.4.6
Technical data
Table 304:
IA, IB, IC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
at currents in the range of 0.01...4.00 × I
n
Current:
±0.5% or ±0.002 × I
n
(at currents in the range of 0.01...4.00 × I
n
)
Phase angle:
±2.5°
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
RMS: No suppression
7.1.5
Three-phase voltage VA, VB, VC
7.1.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase voltage measurement
VMMXU
3U
VA, VB, VC
7.1.5.2
Function block
GUID-5B741292-7FA6-4DEA-8D16-B530FD16A0FE-ANSI V1 EN
Figure 205:
Function block
When using open delta and delta VT connection types in the system,
ignore line-to-neutral voltage values.
1MRS240050-IB C
Section 7
Measurement functions
REF615R
395
Technical Manual