4.2.4.5
Application
A continuous or temporary voltage unbalance can appear in the network for various
reasons. The voltage unbalance mainly occurs due to broken conductors or asymmetrical
loads and is characterized by the appearance of a negative-sequence component of the
voltage. In rotating machines, the voltage unbalance results in a current unbalance, which
heats the rotors of the machines. The rotating machines, therefore, do not tolerate a
continuous negative-sequence voltage higher than typically 1-2 percent x V
n
.
The negative-sequence component current I
2
, drawn by an asynchronous or a
synchronous machine, is linearly proportional to the negative-sequence component
voltage V
2
. When V
2
is P% of V
n
, I
2
is typically about 5 x P% x I
n
.
The negative-sequence overcurrent 46 blocks are used to accomplish a selective
protection against the voltage and current unbalance for each machine separately.
Alternatively, the protection can be implemented with the 47 function, monitoring the
voltage unbalance of the busbar.
If the machines have an unbalance protection of their own, the 47 operation can be applied
as a backup protection or it can be used as an alarm. The latter can be applied when it is
not required to trip loads tolerating voltage unbalance better than the rotating machines.
If there is a considerable degree of voltage unbalance in the network, the rotating
machines should not be connected to the network at all. This logic can be implemented by
inhibiting the closure of the circuit breaker if the 47 operation has picked up. This scheme
also prevents connecting the machine to the network if the phase sequence of the network
is not correct.
An appropriate value for the setting parameter
Voltage pickup value
is approximately 3
percent of V
n
. A suitable value for the setting parameter
Trip delay time
depends on the
application. If the 47 operation is used as a backup protection, the trip time should be set
in accordance with the trip time of 46 used as the main protection. If the 47 operation is
used as the main protection, the trip time should be approximately one second.
4.2.4.6
Signals
Table 193:
47 Input signals
Name
Type
Default
Description
V
2
SIGNAL
0
Negative phase sequence voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Section 4
1MRS240050-IB C
Protection functions
244
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...