The protection relay utilizes Ethernet communication extensively for different purposes.
The exact services depend on the ordered product variant and enabled functionality.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter setting and DFR records can be accessed using the IEC
61850 protocol. Oscillographic files are available to any Ethernet-based application in the
standard COMTRADE format. The protection relay can send and receive binary signals
from other protection relays (so called horizontal communication) using the
IEC61850-8-1 GOOSE profile, where the highest performance class with a total
transmission time of 3 ms is supported. Further, the protection relay supports sending and
receiving of analog values using GOOSE messaging. The protection relay meets the
GOOSE performance requirements for tripping applications in distribution substations, as
defined by the IEC 61850 standard. The protection relay can simultaneously report events
to five different clients on the station bus.
The protection relay can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850, DNP3 and
Modbus. Only one DNP3 client can be supported at a time.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The protection relay can be connected to
Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the
fiber-optic LC connector (100Base-FX).
For the correct operation of redundant loop topology, it is essential that the external
switches in the network support the RSTP protocol and that it is enabled in the switches.
Otherwise, connecting the loop topology can cause problems to the network. The
protection relay itself does not support link-down detection or RSTP. The ring recovery
process is based on the aging of MAC addresses and link-up/link-down events can cause
temporary breaks in communication. For better performance of the self-healing loop, it is
recommended that the external switch furthest from the protection relay loop is assigned
as the root switch (bridge priority = 0) and the bridge priority increases towards the
protection relay loop. The end links of the protection relay loop can be attached to the same
external switch or to two adjacent external switches. Self-healing Ethernet ring requires a
communication module with at least two Ethernet interfaces for all protection relays.
Section 2
1MRS240050-IB C
REF615R overview
38
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...