11.1.2.2
Function block
GUID-C364D2C8-EEA0-4E88-90AB-7922266C673E V1 EN
Figure 277:
Function block
11.1.2.3
Functionality
The minimum second pulse timer function 62CLD-1 contains two independent timers.
The function has a settable pulse length (in seconds). The timers are used for setting the
minimum pulse length for example, the signal outputs. Once the input is activated the
function gives out a pulse (
Cold load time
setting). But if the input remains active longer
than the set
Cold load time
, also the output remains active until the input is deactivated.
GUID-9BE17BA5-70D3-442B-8D24-8544C7A9441A V1 EN
Figure 278:
A = Trip pulse is shorter than Cold load time setting, B = Trip pulse is
longer than Cold load time setting
11.1.2.4
Signals
Table 402:
62CLD-1 Input signals
Name
Type
Default
Description
IN1
BOOLEAN
0=False
Input 1 status
IN2
BOOLEAN
0=False
Input 2 status
Table 403:
62CLD-1 Output signals
Name
Type
Description
OUT1
BOOLEAN
Output 1 status
OUT2
BOOLEAN
Output 2 status
1MRS240050-IB C
Section 11
Other functions
REF615R
535
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...