There is a validation functionality built-in function that checks the relationship adherence
so that if
VVa x time 1
is set higher than
VVa x time 2
or
VVa x time 3
,
VVa x time 2
and
VVa
x time 3
are set equal to the new
VVa x time 1
. If
VVa x time 2
is set higher than
VVa x time 3
,
VVa x time 3
is set to the new
VVa x time 2
. If
VVa x time 2
is set lower than
VVa x time 1
,
the entered
VVa x time 2
is rejected. If
VVa x time 3
is set lower than
VVa x time 2
, the
entered
VVa x time 3
is rejected.
8.3.4.4
Duration measurement
The duration of each voltage phase corresponds to the period during which the measured
TRMS values remain above (swell) or below (dip, interruption) the corresponding limit.
Besides the three limit settings for the variation types dip and swell, there is also a specific
duration setting for each limit setting. For interruption, there is only one limit setting
common for the three duration settings. The maximum duration setting is common for all
variation types.
The duration measurement module measures the voltage variation duration of each phase
voltage separately when the
Phase mode
setting is "Single Phase". The phase variation
durations are independent. However, when the
Phase mode
setting is "Three Phase",
voltage variation may pick up only when all the monitored phases are active. An example
of variation duration when
Phase mode
is "Single Phase" can be seen in
. The
voltage variation in the example is detected as an interruption for the phase B and a dip for
the phase A, and also the variation durations are interpreted as independent
V_B
and
V_A
durations. In case of single-phase interruption, the
DIPST
output is active when either
PICKUP_A
or
PICKUP_B
is active. The measured variation durations are the times
measured between the activation of the
PICKUP_A
or
PICKUP_B
outputs and
deactivation of the
PICKUP_A
or
PICKUP_B
outputs. When the
Phase mode
setting is
"Three Phase", the example case does not result in any activation.
1MRS240050-IB C
Section 8
Power quality measurement functions
REF615R
427
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...