The Synchro check function can operate either with the V_AB or V_A voltages. The
selection of used voltages is defined with the
VT connection
setting of the line voltage
general parameters.
Energizing check
The Energizing check function checks the energizing direction. Energizing is defined as
a situation where a dead network part is connected to an energized section of the network.
The conditions of the network sections to be controlled by the circuit breaker, that is,
which side has to be live and which side dead, are determined by the setting. A situation
where both sides are dead is possible as well. The actual value for defining the dead line
or bus is given with the
Dead bus value
and
Dead line value
settings. Similarly, the actual
values of live line or bus are defined with the
Live bus value
and
Live line value
settings.
Table 377:
Live dead mode of operation under which switching can be carried out
Live dead mode
Description
Both Dead
Both line and bus de-energized
Live L, Dead B
Bus de-energized and line energized
Dead L, Live B
Line de-energized and bus energized
Dead Bus, L Any
Both line and bus de-energized or bus de-energized
and line energized
Dead L, Bus Any
Both line and bus de-energized or line de-energized
and bus energized
One Live, Dead
Bus de-energized and line energized or line de-
energized and bus energized
Not Both Live
Both line and bus de-energized or bus de-energized
and line energized or line de-energized and bus
energized
When the energizing direction corresponds to the settings, the situation has to be constant
for a time set with the
Energizing time
setting before the circuit breaker closing is
permitted. The purpose of this time delay is to ensure that the dead side remains de-
energized and also that the situation is not caused by a temporary interference. If the
conditions do not persist for a specified operation time, the timer is reset and the procedure
is restarted when the conditions allow. The circuit breaker closing is not permitted if the
measured voltage on the live side is greater than the set value of
Max energizing V
.
The measured energized state is available as a monitored data value ENERG_STATE and
as four function outputs
LLDB
(live line / dead bus),
LLLB
(live line / live bus),
DLLB
(dead line / live bus) and
DLDB
(dead line / dead bus), of which only one can be active at
a time. It is also possible that the measured energized state indicates “Unknown” if at least
one of the measured voltages is between the limits set with the dead and live setting
parameters.
Section 9
1MRS240050-IB C
Control functions
498
REF615R
Technical Manual
Содержание RELION REF615R
Страница 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Страница 2: ......
Страница 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Страница 28: ...22 ...
Страница 36: ...30 ...
Страница 46: ...40 ...
Страница 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Страница 118: ...112 ...
Страница 318: ...312 ...
Страница 388: ...382 ...
Страница 456: ...450 ...
Страница 520: ...514 ...
Страница 652: ...646 ...
Страница 656: ...650 ...
Страница 658: ...652 ...
Страница 663: ...657 ...